MVI46-PDPMV1 ♦ SLC Platform

Reference

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 119 of 160

March 25, 2011

M1 Word Offset

Description

45 to 46

Module configuration checksum for module configuration downloaded from

configuration utility

47

Module program scan counter. Can be used to gauge application code scan

time performance

48

Module PROFIBUS output image data update counter - Counter representing
the number of times the output data image is transferred to the module's

internal Master

49

Module PROFIBUS input image data update counter - Counter representing
the number of times the input data image is transferred from the module's

internal Master.

50

Module out mailbox counter

51

Module in mailbox counter

52

Module alarm IND receive counter - Number of spontaneous alarm

messages received from slave.

53

Module alarm CON receive counter - Number of confirmation messages

received from slaves indicating that the slave received the confirmation

message from the module

54

Module acyclic read request message counter - Number of acyclic read

request messages processed by the module

55

Module acyclic write request message counter - Number of acyclic write

request messages processed by the module

56

Module backplane read count - Rollover counter of the number of module to

processor backplane read data transfers

57

Module backplane write count - Rollover counter of the number of module to

processor backplane write data transfers

58

Module backplane error count - Rollover counter of the number of module to

processor backplane data transfers that have failed

59

File Error Word - This is a bitmapped value that indicates which files are not

present.
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Not Used
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR LED on the module will

be illuminated.

60 to 72

Reserved for future use (13 words)

73

In mailbox queue count - Number of message in the in mailbox queue

74

Out mailbox queue count - Number of message in the out mailbox queue

75

Alarm queue count - Number of message in the alarm queue

76

Last out mailbox message ID processed from output image

77

Current in mailbox control index

78

Current alarm control index

Advertising