Mailbox Messaging

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 68 of 160

ProSoft Technology, Inc.

March 25, 2011

Slave Address
Range 1 to 125; 127
If the request applies for only one slave, that slave address must be entered in

the range 1 to 125. If a slave group is to be addressed, slave address should be

127 (multicast address).

Group Select
Range 01h to FFh (Bit Coded)
This parameter determines which group to address. Refer to the following

example:

b7

b6

b5

b4

b3

b2

b1

b0

Group 8

Group 7

Group 6

Group 5

Group 4

Group 3

Group 2

Group 1

Example:

To address Group 1, 2, and 4, the Group Select value should be D0h. If an

individual slave should be addressed, the correct group selection must also be

made, because the slave will ignore the message if it does not belong to the

requested group(s).
What group(s) a slave belongs to is determined during network configuration,

and is downloaded during initialization to each slave via the PROFIBUS telegram
Set_Prm.

Control Command
This parameter specifies the command to send:

Bit

Explanation

0 (LSB)

Reserved, set to zero

1

Reserved, set to zero

2

Unfreeze input data

3

Freeze input data

4

Unsynchronize output data

5

Synchronize output data

6

Reserved, set to zero

7 (MSB)

Reserved, set to zero

Combinations of the bits (Unsync/Sync and Unfreeze/Freeze)

Bits 0 or 6

Bits 1 or 7

Explanation

0

0

No function

0

1

Function will be activated

1

0

Function will be inactive

1

1

Function will be inactive