MVI46-PDPMV1 ♦ SLC Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 73 of 160

March 25, 2011

Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 90).

Slave Address
Range 1 to 125; specifies the slave from which to read the configuration.

Error Code [1 … 4]
If "Return Code" equals 3080h ("Negative indication from lower layer"), status

values according to the DP-specification may be available in "Error Code 1",

Error Codes 2 through 3 are reserved. Refer to Mailbox Messaging Error Codes

(page 90).

Return Code
Refer to Mailbox Messaging Error Codes (page 90).

Fault Information
If "Invalid other" is returned in the Acyclic Message Status Word in the header of

the response, information about the fault can be found here. Refer to Acyclic

Message Status Word (page 90).
0100h: Address out of range.
0A00h: Failed to execute request. Refer to Return Codes (page 91) for additional
information.
0B00h: Remote station failure. Refer to Return Codes (page 91) for additional

information.
FF00h: Module not initialized.

Identifier Bytes [1 … n]
Refer to EN50170 Vol. 2 for information on the structure of these bytes. In

addition, refer to the documentation provided with the slave device for more

information.

4.2.4 Mailbox Message: Set Slave Address

This command makes it possible to set the node address of a specified slave, if

the slave supports this feature.

Note: The message data size depends on the actual slave implementation. Range 0 to 240 bytes.

Parameter

Description

Command Initiator

Application

Command Name

SET SLAVE ADDRESS

Command Number

0600h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.