ProSoft Technology MVI46-PDPMV1 User Manual
Page 56

Configuring the MVI46-PDPMV1 Module
MVI46-PDPMV1 ♦ SLC Platform
User Manual
PROFIBUS DPV1 Master
Page 56 of 160
ProSoft Technology, Inc.
March 25, 2011
2.4.4 Viewing the Data Files in RSLogix 500
Note: For this procedure, you must connect a serial cable from the serial port on your PC to the
DB9M connector on the SLC processor.
1 Open the sample ladder logic in RSLogix 500.
2 Open the C
OMMUNICATIONS
menu, and choose G
O
O
NLINE
.
3 In the Project Browser window, double-click N11 data file.
4 Verify that N11:20 is the last word of the slave configured list
The bit in N11:20/13 is set, indicating that slave 125 is configured.
5 Next, check the slave data exchange list at N11:28
The bit in N11:28/13 is set, indicating that slave 125 is exchanging data.