Reference

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 120 of 160

ProSoft Technology, Inc.

March 25, 2011

Mailbox Communication
Mailbox requests are built and sent through ladder logic according to the data

listed in the BLD_MB routine.
The module immediately responds with a confirmation message consisting of the

Mailbox Out Message Response to the processor.
After the mailbox request is processed by the module, it sends the Mailbox In

Message to the processor. Note that the ladder should refer to the command

data to copy the mailbox response to the correct data file. For example:

command = 02 => Set Operating Mode Response 1

Input Data
This section contains the PROFIBUS Cyclic Input data received from the slave or

slaves.

M0 Output Image

Output Data Area Map (M0 File)

M0 Word Offset

Description

0

Last in mailbox control index

1

Last alarm control index

2 to 3

PROFIBUS CRC32

4 to 5

Module CRC32

6 to 149

Out Mailbox Acyclic Data

150 to n

PROFIBUS Cyclic Output Data

6.2.3 PROFIBUS DP Architecture

The PROFIBUS DPV1 network supports multiple Master systems with several

slaves.
The following table shows the most important features of PROFIBUS DPV1:

Standard

EIN 501 70
DIN 19245

Transmission equipment (Physical) EIA RS-485

IEC 1158-2 (through link or coupler)
Fiber Optic Cable (not available)

Transfer procedure

Half-duplex

Bus topology

Linear bus with active bus termination

Bus cable type

Shielded twisted pair conductors

Connector

9-pin D-Sub

Number of nodes on the bus

Max: 32 with no repeaters
Max: 125 with 3 repeaters in 4 segments