ProSoft Technology MVI46-PDPMV1 User Manual

Page 99

Advertising
background image

MVI46-PDPMV1 ♦ SLC Platform

Diagnostics and Troubleshooting

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 99 of 160

March 25, 2011

5.4

PROFIBUS Master Indicators

LED

State

Description

TKN HLD

GREEN

The module has the token

DBASE

STAT

GREEN

Database OK

MSTR STAT GREEN

Operating mode

GREEN-Flashing Clear mode

RED

Stop mode

OFF

Offline

GREEN-Flashing Database download in progress
GREEN 1 second/

RED 2 seconds

Module in Legacy mode while the Flex ladder is loaded to the

processor. Check processor program.

RED

Invalid database

OFF

No databases have been downloaded

COM STAT GREEN

Data exchange with all configured slaves

GREEN-Flashing Data exchange with at least one of the configured slaves
RED

Bus control error (possible bus short circuit or configuration

error)

OFF

No data exchange with any configured slave

OFF

The module does not have the token

ALL LEDs

RED

Fatal error