ProSoft Technology MVI46-PDPMV1 User Manual

Page 114

Advertising
background image

Reference

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 114 of 160

ProSoft Technology, Inc.

March 25, 2011

6.2

Functional Overview

The MVI46 module communicates with the processor over the backplane using

only the following two data files:
 M1 Data File
 M0 Data File
This section of the Application Reference Guide describes the data structures

and transfer mechanisms used to transfer data between the MVI46-PDPMV1

module and the SLC processor using these files.

6.2.1 About the PROFIBUS Protocol

PROFIBUS (Process Field Bus) is a widely-used, open-standards protocol

created by a consortium of European factory automation suppliers in 1989.
PROFIBUS is a Master/slave protocol. The Master establishes a connection to

one or more remote slaves. When the connection is established, the Master

sends the PROFIBUS poll messages (called telegrams in PROFIBUS) to the

slave or slaves. The MVI46-PDPMV1 module works as a Master only. It cannot

be a slave to some other Master.
The MVI46-PDPMV1 module also acts as an input/output module between

devices on a PROFIBUS network and the Rockwell Automation SLC processor.

The module uses an internal database to pass data and mailbox requests and

responses between the processor and the slave devices on the PROFIBUS

network.
PROFIBUS specifications include a variety of network types. The network type

supported by the MVI46-PDPMV1 module is PROFIBUS DP version 1.0, which is

designed for remote I/O systems, motor control centers, and variable speed

drives.