MVI46-PDPMV1 ♦ SLC Platform

Diagnostics and Troubleshooting

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 107 of 160

March 25, 2011

Viewing PROFIBUS Data
Press [2] to view PROFIBUS data. Use this command to view information related
to the status of each slave in the PROFIBUS network, and to verify that each

slave is configured (SLAVE CFG LIST), exchanging data with the Master

(TRANSFER LIST) and in diagnostic mode (SLAVE DIAG LIST).
You can also check the module's operation state, where:
 00 = Offline
 40 = Stop
 80 = Clear
 C0 = Operate

Viewing Control Registers
Press [3] to view information about the PROFIBUS Master’s Control Registers.

Use this command to view general information about the module, such as the

firmware version and its serial number. The module status contains two possible

codes:
 0400 = module is running but not communicating with slaves
 0401 = module is running and communicating with slaves
If the module is in STOP mode, the status code is displayed as 0400.

Exiting the Program
Press [ESC]

to restart the module and force all drivers to be loaded. The module

will use the configuration stored in the module's flash memory to configure the

module.