Configuring the MVI46-PDPMV1 Module

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 50 of 160

ProSoft Technology, Inc.

March 25, 2011

2.4

Verifying Correct Operation

The final step is to verify that the MVI46-PDPMV1 module is communicating with

the PROFIBUS slave. Choose the method that best suits your connection and

proximity to the modules and the processor.
 If you are able to view the module directly: Look at the PROFIBUS LEDs on

the MVI46-PDPMV1 (page 50)

 If you are able to connect to the module using ProSoft Configuration Builder

and a serial cable: View the online status of the PROFIBUS network (page

51)

 If you are able to connect to the module using ProSoft Configuration Builder

and a serial cable: View the Fieldbus Data from the MVI46-PDPMV1’s

Configuration/Debug menu (page 53)

 If you are able to connect to the processor using RSLogix 500: View the Data

Files in RSLogix 500 (page 56)

 If you are able to connect to the processor using RSLogix 500: Send a

Mailbox Message in RSLogix 500 (page 58)

2.4.1 Checking the PROFIBUS LEDs on the MVI46-PDPMV1

 If all four PROFIBUS LEDs (page 99) are illuminated green, then the

PROFIBUS Master is communicating and exchanging data with all configured

PROFIBUS slaves.

 If the COM STAT LED is green and flashing, the PROFIBUS Master is

communicating and exchanging data with at least one of the configured

slaves.

 If the COM STAT LED is red, there is a communication or configuration error.
 If the COM STAT LED is off, the PROFIBUS Master is not communicating

with any slaves. The most likely reason is that the slaves are not correctly

configured.

 After restarting the MVI46-PDPMV1 Master and the PROFIBUS slave, look at

the PROFIBUS cable connection. If all the PROFIBUS LEDs on the MVI46-

PDPMV1 are illuminated green, then the Master is communicating

successfully with all slaves.