Configuring the MVI46-PDPMV1 Module

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 38 of 160

ProSoft Technology, Inc.

March 25, 2011

GSD Selection Algorithm

If two or more matching GSD-files are found, the first one found should be

selected. The other compatible files should be stored so that the user can select

one of them instead. If the user selects another GSD-file, the PROFIBUS Master
Configuration
window will run through the Module Selection Algorithm (described

below) again.

Module Selection Algorithm

The algorithm used to find modules in the GSD based on the Identifier byte(s) is

as follows:
Select the module that matches the largest number of Identifier bytes. If the GSD

contains two or more modules with the exact set of Identifier bytes, use the first

module found.
Example:
If a slave responds with identifier bytes: 0x11, 0x21, 0x31 and that the associated

GSD-file contains five modules: “A” = 0x11, “B” = 0x21, “C” = 0x31, “AB” = 0x11,

0x21 and “BC” = 0x21, 0x31. The PROFIBUS Master Configuration window will

then select modules "AB" and "C".

Note: If no matching module is found in the GSD, The PROFIBUS Master Configuration window
will display the identifier byte(s) instead.


Network scan window
The information extracted from the GSD-file(s) will be displayed in the Network
scan
window.

Select

In this column all found slaves will be marked as selected by default, except for

slaves with the special address 126 (refer to the next section that describes the

Address column). Only selected slaves will be added to the PROFIBUS Master
Configuration
when the

A

DOPT SELECTED SLAVES

button is clicked.


Address

In this column the node address of the slaves will be displayed. Found slaves

should be listed in ascending order according to their node addresses.