Mailbox Messaging

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 76 of 160

ProSoft Technology, Inc.

March 25, 2011

4.2.5 Mailbox Message: Get Live List

This command returns 127 bytes of information about the nodes on the network.

Every byte stands for one bus subscriber, and the position of the byte in the

response data assigns the address (0 to 126), the content assigns the Station

Type.
This command can be sent in all operation modes (STOP, CLEAR, and

OPERATE), however the module must be initialized properly.

Parameter

Description

Command Initiator

Application

Command Name

GET LIVE LIST

Command Number

1800h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.

Command and Response Layout: Get Live List

Command

Response

Message ID

(ID)

(ID)

Message information

4002h

0002h

Command

0018h

0018h

Get Live List

Data size

0000h

0007h

127 Bytes of Data

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

-

-

Extended word 2

-

-

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

-

Extended word 6

-

-

Extended word 7

-

Return Code

Extended word 8

-

Fault Information

Message Data byte 1

Station Type 0

Response Data Byte 1

Message Data byte 2

Station Type 1

Response Data Byte 1

Message Data byte 3

Station Type 2

Response Data Byte 1

...

...

Response Data Byte 1

Message Data byte "n"

Station Type 126

Response Data Byte 1