ProSoft Technology MVI46-PDPMV1 User Manual

Page 146

Advertising
background image

Reference

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 146 of 160

ProSoft Technology, Inc.

March 25, 2011

6.9

Constructing a Bus Cable for PROFIBUS DP

The bus cable for connecting PROFIBUS DP devices must be constructed by the

user. A special PROFIBUS cable (twisted pair) is required here. This standard

cable is available from various manufacturers and is a Belden part number

3079A.
If you plan to construct your own bus cable, the following part numbers are

provided for your convenience.
 PROFIBUS connector: Siemens part number 6ES7972-0BA40-0XA0
 PROFIBUS cable: Belden part number 3079A.
To construct the cable, proceed as follows:
1 Cut the cable to the required length.
2 Prepare the cable ends as shown in the illustration (dimensions in mm):

J PVC Jacket
S Braided shielding

3 Remove the PVC jacket J to the indicated length.
4 Wrap the provided copper shielding F around the shield braiding S:

J PVC jacket
S Braided shielding
F Copper foil shielding

Additional foil can be obtained from 3M.

5 Plug the leads of the corresponding cable(s) into the terminals as shown:

o

Green leads in terminal A

o

Red lead in terminal B

 Note: Do not tighten the corresponding screws yet.