Mailbox Messaging

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 88 of 160

ProSoft Technology, Inc.

March 25, 2011

Command:

 Message data word 1-63

Byte-array stating which slave/slaves to stop. Array index is equal to slave

address.

0: Do not affect slave

1: Stop slave

2-255: Reserved

Response:

 Message information (in response header)

"Invalid Data Size" is returned if Data size in the command header does not

equal 126.

If "Invalid Other" is returned, further information is to be found in Extended

word 8.

 Additional Fault information (Extended word 7)

If Extended word 8 equals 0x000A -"Failed to execute request" additional info

can be found here.

 Fault information (Extended word 8)

0x0001: Invalid setting in Message data word 1-63 of the command.

0x0002: At least one slave reports a warning. Refer to Message data word 1-

63.

0x000A: Failed to execute request. Additional fault information is to be found

in Extended word 7.

0x00FE: Command not possible; module operates as class 2 Master only.

0x00FF: Module not initialized (this command is only possible after

END_INIT).

 Message data word 1-63

Byte-array stating the status of the slaves. Array index is equal to slave

address.

0: Slave unaffected

1: Slave stopped

2: Warning - Slave could not be stopped because it is not part of the

configuration

3: Warning - Slave already stopped