ProSoft Technology MVI46-PDPMV1 User Manual

Page 82

Advertising
background image

Mailbox Messaging

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 82 of 160

ProSoft Technology, Inc.

March 25, 2011

Command and Response Layout: Alarm Indication

Command

Response

Message ID

(ID)

(ID)

Message information

4002h

0002h

Command

0022h

0022h

Alarm Indication

Data size

(request length)

0000h

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

Slave

Address

Slot Number

-

Extended word 2 Seq Number Alarm Spec

Ack

-

Extended word 3 Alarm Type

Ext Diag

-

Extended word 4

-

-

Extended word 5

-

-

Extended word 6

-

-

Extended word 7

-

-

Extended word 8

Fault Information

-

Message Data byte 1

Data 1

Message Data byte 2

Data 2

Message Data byte 3

Data 3

Message Data byte n

Data n

Slave Address
Station address of the slave that issued the alarm.

Slot Number
Used by the slave to indicate the source of the alarm. Range 0 to 254.

Seq Number
Unique identification number of the alarm. Range 0 to 31.