Reference

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 118 of 160

ProSoft Technology, Inc.

March 25, 2011

Slave List Structure for Offset Words 13, 21 and 29

PROFIBUS Master Status Data (M1 Word Offsets 37 to 78)

M1 Word Offset

Description

37

Low byte: Not used

High byte: PROFIBUS Master operating state
0x0000=Offline
0x4000=Stop
0x8000=Clear
0xC000=Operate

38

PROFIBUS Master PNO identification number (Bytes will be swapped)
Low byte: Most significant byte (MSB)
High byte: Least significant byte (LSB)

39 to 40

Unique 32-bit serial number for the PROFIBUS Master

41

Software version number for the PROFIBUS Master software.
Low byte: Most significant byte (MSB)
High byte: Least significant byte (LSB)
Example for Version 1.40:
High Byte: 0x40
Low Byte: 0x01

42

PROFIBUS Master module’s operating status
Low byte: Most significant byte (MSB)
High byte: Least significant byte (LSB)
Bit 2=Application Status
0: Application Stopped
1: Application Running
Bit 8=data exchange (FBRS)
0: There is no data exchange with any of the assigned slaves
1: There is Data Exchange with at least one of the assigned slaves
Bit 9=slave input frozen/cleared (FBFC)
0: A slave's inputs in the IN area are cleared if a slave is not in Data

Exchange
1: A slave’s inputs in the IN area are frozen if a slave is not in Data Exchange
Bit 12=reset (RDR)
0: No action
1: A reset is requested by the PROFIBUS Master module because a new

database has been downloaded

43 to 44

CRC32 checksum for PROFIBUS Master configuration downloaded from

configuration utility