General commands, Generic functions, Type 1 - time-tagged – ProSoft Technology MVI46-103M User Manual

Page 168

Advertising
background image

MVI46-103M ♦ SLC Platform

Reference

IEC 60870-5-103 Master Communication Module

Page 168 of 187

ProSoft Technology, Inc.

September 12, 2006

General commands

Fun

128 160 176 192 254 255

Inf Description

Com Type

t(z) l>>

∆l

T

∆l

L

GEN GLB

16 auto-recloser

on/off

On/Off

20 X X X

17 teleprotection on/off

On/Off 20

X

X

18 protection

on/off

On/Off

20 X X X X

19 LED

reset

On 20 X X X X

23 activate characteristic 1

On

20

X

24 activate characteristic 2

On

20

X

25 activate characteristic 3

On

20

X

26 activate characteristic 4

On

20

X


Generic functions

Fun

128 160 176 192 254 255

Inf

Description

Type

t(z)

l>>

∆l

T

∆l

L

GEN GLB

240 read headings of all defined groups

21

X

241 read values or attributes of all entries of

one group

21

X

243 read directory of a single entry

21

X

244 read value or attribute of a single entry

21

X

245 general interrogation of generic data

21

X

248 write entry

10

X

249 write entry with confirmation

10

X

250 write entry with execution

10

X

251 write entry abort

10

X


7.8.6 Definition

and

Presentation of ASDU'S In Monitor

Direction

Type 1 - Time-tagged

Bytes Description

Spec

1

Value of 1

1 0x81

1 COT

1

Common address of ASDU

1 Function

Type

Advertising