Functional Overview

MVI46-103M ♦ SLC Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 23 of 187

September 12, 2006

Block Format for Read

Word Offset in
Block

Data Field(s)

Description

4200 Block

ID

This field contains the block identification code of 9903 for the
block.

4201 Event

Count

This field contains the number of events present in the block.
Values of 1 to 20 are valid.

4202-4211

Event 1

Event message

4212-4221

Event 2

Event message

4222-4231

Event 3

Event message

4232-4241

Event 4

Event message

4242-4251

Event 5

Event message

4252-4261

Event 6

Event message

4262-4271

Event 7

Event message

4272-4281

Event 8

Event message

4282-4291

Event 9

Event message

The format of each 10-word data region in the block is as follows:

Word Offset

Definitions

Description

0

Session Index/Sector
Index

This field contains the session and sector indices
used to define the controlled unit in the module from
which the event was generated. The MSB contains
the session index and the LSB contains the sector
index.

1 ASDU

Type

This field contains the ASDU type code for the data
contained in the message.

2

Function Code/Point
Index*

This field contains the function code and the point
index associated with the event message. The MSB
contains the function code and the LSB contains the
point index.

3 Fault

Number

This is the fault number for the event if applicable.
Only valid for ASDU types 2 and 4.

4 Sec/mSec

This word contains the seconds and millisecond
values with a range of 0 to 59999 time at which the
message was generated by the slave device.

5 Hr/Min. This word contains the hour and minutes the

message was generated by the slave. The MSB
contains the hour and the LSB contains the minute
value.

6 Invalid/DST

This word contains two bits that relate to the time
value recorded in the slave device for the message.
Bit 0 corresponds to the validity of the time (0=valid,
1=invalid) and Bit 1 defines if daylight savings time is
used in the time (0=no, 1=yes).

7 Relative

Time

This field contains the relative time value if
applicable to the object. Only valid for ASDU types 2
and 4.