[Section]/Item Value

Range

Description

Data Link Address:

0 to 254

This parameter uniquely defines the data
link address for this unit on the
communication channel The ranges of
values are from 0 to 254. Address 255 is
the broadcast address.

Failure Delay:

0 to 2000

This parameter sets the minimum number
of seconds to delay before polling this
session when it is not online. This
parameter is only used in unbalanced
mode.

Confirm Timeout:

0 to 2^32–1 This parameter sets the number of

milliseconds to wait for a confirm response
from the controlled device.

Retry Count:

0 to 255

This parameter sets the number of retries
to be performed on the controlled device
when a communication error occurs.

C1/C2 Poll Count Pend:

0 to 100

This parameter sets the maximum number
of class 1 and class 2 polls performed on
this session before trying the next session.
This parameter prevents a session from
monopolizing the communication port.

Class 1 Polls:

0 to 65535 This parameter sets the maximum number

of class one polls performed on this
session before switching to another
session. This parameter prevents a session
from monopolizing the communication port.

Class 1 Pend Delay:

0 to 2^32–1 This parameter sets the minimum number

of milliseconds to delay between class 1
polls for pending data.

Class 2 Pend Delay:

0 to 2^32–1 This parameter sets the minimum number

of milliseconds to delay between class 2
polls for pending data.

Class 1 Poll Delay:

0 to 2^32–1 This parameter sets the minimum number

of milliseconds to delay between each
class 1 poll.

Class 2 Poll Delay:

0 to 2^32–1 This parameter sets the minimum number

of milliseconds to delay between each
class 2 poll.

Response Timeout:

0 to 2^32–1 This parameter sets the maximum number

of milliseconds to wait for a confirmation
from the controlled station to a request
from this module.

[Section]/Item Value

Range

Description

[IEC-103 MASTER SESSION x
SECTOR y]

This section sets the parameters for a
specific sector of a session.