Functional Overview

MVI46-103M ♦ SLC Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 21 of 187

September 12, 2006

Word Offset in
Block

Data Field(s)

Description

4100

Block ID

This field contains the block identification code of 9901
for the block.

4101

Command Count

This field defines the number of user commands
contained in the block. The valid range for the field is 1
to 8.

4102 to 4111

Command #1

Data required to build the user defined command in the
command queue.

4112 to 4121

Command #2

Data required to build the user defined command in the
command queue.

4122 to 4131

Command #3

Data required to build the user defined command in the
command queue.

4132 to 4141

Command #4

Data required to build the user defined command in the
command queue.

4142 to 4151

Command #5

Data required to build the user defined command in the
command queue.

4152 to 4161

Command #6

Data required to build the user defined command in the
command queue.

4161 to 4171

Command #7

Data required to build the user defined command in the
command queue.

4172 to 4181

Command #8

Data required to build the user defined command in the
command queue.

The following fields are used for each 10-word record in the command list:

Word Offset

Definitions

Description

0

Database Index

Address in module to associate with the command.

1 Session

Index

Session index defined in the module to associate with
the command.

2

Sector Index

Sector index for session as defined in the module.

3

Data Type

ASDU data type associated with the command.

4

Function Code

Function Code for the command.

5

Point Index *

*Information

Number

Information object address for the point on which the
command operates.

6

Override Flag

Override flag for general command.

7

Override Value

Override value for general command.

8

Reserved

Reserved for future use.

9

Reserved

Reserved for future use.

Refer to the command list section of this documentation for a detailed definition
of the fields contained in this block. They are the same as those used in
constructed the commands in the command list.

There is no response block built by the module to send back to the processor
after the block is processed. The module will set register 4100 to a value of zero
after the commands have been processed. The commands are placed in the
command queue and issued at a high priority.