7.5 MVI46-103M

Configuration File Example

This section contains a listing of an example IEC103M.CFG file for the MVI46-
103M module.

# IEC103M.CFG

#

# Example file for use with the IEC-870-5-103 Master protocol driver on the

# MVI46 platform (two master ports).

#

[Backplane Configuration]

Module Name : MVI46-103M DEMO MODULE

Failure Flag Count : 0 #Determines if BP failure will cause protocol to be

#disabled (0=Ignore, >0 = failure count to disable)

Pass-Through Events : Y #Pass event messages to processor

# This is the configuration for the IEC-870-5-103 master port emulated on the

# module.

[IEC-870-5-103 Master]

Session Count : 1 #1 to 32 - maximum number of slaves on all channels

[IEC-870-5-103 Master Port 0]

# Communication Parameters

Baud Rate : 19200 #Baud rate for port 110-115200

Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space

RTS On : 0 #0-65536 mSec before message

RTS Off : 0 #0-65536 mSec after message

Minimum Delay : 10 #Minimum # of mSec before response sent

Receive Timeout : 2000 #Maximum mSec from first char to last to wait

# These parameters are protocol specific

Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N)

[IEC-870-5-103 Master Port 1]

# Communication Parameters

Baud Rate : 19200 #Baud rate for port 110-115200

Parity : E #N=None, O=Odd, E=Even, M=Mark, S=Space

RTS On : 0 #0-65536 mSec before message

RTS Off : 0 #0-65536 mSec after message

Minimum Delay : 5 #Minimum # of mSec before response sent

Receive Timeout : 1000 #Maximum mSec from first char to last to wait

# These parameters are protocol specific

Single char ACK F0,1 or 3 : Y #Single E5 resp to ACK func 0, 1 & 3 req (Y/N)

# This section is used to define session 0 which runs on Port 0

[IEC-103 Master Session 0]

Communication Port : 0 #Index of COM port for session (0 or 1)

Sector Count : 5 #5 is max for this version of app

Data Link Address : 0 #Range is 0 to 65535 DL address of slave

Failure Delay : 3 #Min Sec to delay before poll of offline slave

#(0 to 2000 seconds)