Error Description

902

Negative COT in response

903

Session is offline

904

Session is disabled

905

Select confirmation received, waiting to execute

906

Execute confirmation has not be received


7.4 MVI46-103M

Configuration Data Definition

This section contains a listing of the parameters and their definitions for the
MVI46-103M module configuration file definition (IEC103M.CFG).

7.4.1 MVI46

IEC

60870-5-103 Master Communication

Module Configuration

[Section]/Item Value

Range

Description

[Backplane Configuration]

Backplane transfer parameters

Module Name:

0 to 80
characters

This parameter assigns a name to the
module that can be viewed using the
configuration/debug port. It can be used to
identify the module and the configuration
file.

Failure Flag Count:

0 to 65535 This parameter specifies the number of

successive transfer errors that must occur
before the communication ports are shut
down. If the parameter is set to 0, the
communication ports will continue to
operate under all conditions. If the value is
set larger than 0 (1-65535),
communications will cease if the specified
number of failures occur.

Pass-Through Events:

Y or N

This parameter specifies if event messages
received on the master ports will be passed
to the processor. If the parameter is set to
N, event messages will not be passed to
the processor. If the parameter is set to Y,
the module will pass all events received to
the processor using block identifier 9903.

[Section]/Item Value

Range

Description

[IEC 60870-5-103 MASTER]

Module level parameters

Session Count:

1 to 32

This parameter specifies the maximum
number of session to establish on the
module. This corresponds to the number of
slaves to be interfaced with the module.
This value represents the total number of
slaves on both ports combined.

Advertising