ProSoft Technology MVI46-103M User Manual

Page 91

Advertising
background image

Reference MVI46-103M

♦ SLC Platform

IEC 60870-5-103 Master Communication Module

ProSoft Technology, Inc.

Page 91 of 187

September 12, 2006

# 255 Global function type

#

# Database Index = Database address in module

#

# ASDU Database Function Point

# Type Index Code Index

START

2 480 128 64

2 496 128 65

2 512 128 66

2 528 128 67

2 544 128 68

2 560 128 69

2 576 128 70

2 592 128 71

2 608 128 72

2 624 128 73

END

[IEC-103 Master Session 0 Sector 4]

Common ASDU Address : 4 #Range 0 to 255 Sector address

#Req init requests when session first online (not req if slave sends

# EOI sequence)

Online Time sync : Y #Send time sync message when first online

Online General Int : Y #Send general interrogation

#Req init requests when EOI (end of initialization) received from slave

EOI Time sync : Y #Send time sync message when first online

EOI General Int : Y #Send general interrogation

# Database definition for this session/sector

# Types are as follows:

#

# Monitored ASDU Types

# 1 = Time-tagged message (bit addressed with 2 bits/point)

# 2 = Time-tagged message with relative time (bit addressed with 2 bits/point)

# 3 = Measurands I (4 word values using word address using double-word address)

# 4 = Time-tagged measurands with relative time (1 float value)

# 5 = Identification (12 characters using a byte address)

# 9 = Measurands II (9 word values using word address)

#

# Point Index is the information object number in the slave unit.

# ASDU Index Description

# 1 Bit address with each point occupying 2 bits

# 2 Bit address with each point occupying 2 bits

# 3 Word address with each point occupying 4 words

# 4 Double-word address for the single float value

# 5 Byte address with each point occupying 12 bytes

# 9 Word address with each point occupying 9 words

#

# Function Code Values

# Code Definition

# 128 Distance protection

# 160 Overcurrent protection