Operation – MITSUBISHI ELECTRIC MR-J2S- CL User Manual

Page 102

Advertising
background image

4 - 19

4. OPERATION

(e) Interrupt positioning command (ITP)

POINT

When Interrupt positioning (ITP) is used for positioning, a stop position
differs depending on the servo motor speed provided when the "ITP"

command is enabled.

When the "ITP" command is used in a program, the axis stops at the position by the set value
farther from the position where any of Program input 1 to 3 (PI1 to PI3) turned ON.
If the move command set with the "MOV", "MOVI", "MOVA" or "MOVIA" command is less than the
set value of the "ITP (set value)" command, the program proceeds to the next step without
executing the "ITP (set value)" command.
When using the "ITP" command, always place the "SYNC" command immediately before the "ITP"
command.

1) Program example 1

Program

Description

SPN (500)
STA (200)
STB (300)
MOV (600)
SPN (100)
MOVA (600)
SYNC (1)
ITP (200)
STOP

Speed (Motor speed)

500 [r/min]

Acceleration time constant

200 [ms]

Deceleration time constant

300 [ms]

Absolute move command

600 [ 10

STM

m]

Speed (Motor speed)

100 [r/min]

Absolute continuous move command

600 [ 10

STM

m]

Step is suspended until Program input (PI1) turns ON.

a)

Interrupt positioning command

200 [ 10

STM

m]

b)

Program end

P1

0r/min

ON

OFF

Servo motor
speed

Forward
rotation

Program input1
(PI1)

P1 b)

Waiting for PI1 to be turned ON
by SYNC(1) (a))

(200 10

STM

m)