13 - 7

13. CHARACTERISTICS

13.5 Inrush Currents at Power-On of Main Circuit and Control Circuit

The following table indicates the inrush currents (measurement data) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply equipment capacity of 2500kVA and the
wiring length of 10m.

Inrush Currents (Aop)

Servo Amplifier

Main circuit power supply (L1-L3)

Control circuit power supply (L11-L21)

MR-J2S-10CL 20CL

30A

(Attenuated to approx. 5A in 10ms)

MR-J2S-40CL 60CL

30A

(Attenuated to approx. 5A in 10ms)

MR-J2S-70CL 100CL

54A

(Attenuated to approx. 12A in 10ms)

70 to 100A

(Attenuated to approx. 0A in 0.5 to 1ms)

MR-J2S-200CL 350CL

120A

(Attenuated to approx. 12A in 20ms)

100 to 130A

(Attenuated to approx. 0A in 0.5 to 1ms)

MR-J2S-500CL

44A

(Attenuated to approx. 20A in 20ms)

MR-J2S-700CL

88A

(Attenuated to approx. 20A in 20ms)

30A

(Attenuated to approx. 0A in several ms)

Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to Section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be
tripped by an inrush current.