11. TROUBLESHOOTING

Display

Name

Definition

Cause

Action

AL.17

Board error

CPU/parts fault

AL.19

Memory error 3 ROM memory fault

Faulty parts in the servo amplifier

Checking method

Alarm (A.17 or A.18) occurs
if power is switched on after
disconnection of all cables
but the control circuit power
supply cables.

Change the servo amplifier.

AL.1A Motor

combination

error

Wrong combination

of servo amplifier

and servo motor.

Wrong combination of servo amplifier

and servo motor connected.

Use correct combination.

1. Encoder connector (CN2)

disconnected.

Connect correctly.

2. Encoder fault

Cange the servo motor.

AL.20

Encoder error 2 Communication

error occurred

between encoder and

servo amplifier.

3. Encoder cable faulty

(wire breakage or shorted)

Repair or change the cable.

1. Power input wires and servo motor

output wires are in contact at main

circuit terminal block (TE1).

Connect correctly.

2. Sheathes of servo motor power

cables deteriorated, resulting in

ground fault.

Change the cable.

AL.24

Main circuit

error

Ground fault

occurred at the servo

motor outputs (U,V

and W phases) of the

servo amplififer.

3. Main circuit of servo amplifier

failed.

Checking method

AL.24 occurs if the servo is
switched on after disconnecting
the U, V, W power cables from
the servo amplifier.

Change the servo amplifier.

1. Reduced voltage of super capacitor

in encoder

After leaving the alarm occurring for a few

minutes, switch power off, then on again.

Always make home position setting again.

2. Battery voltage low

Absolute position

data in error

3. Battery cable or battery is faulty.

Change battery.

Always make home position setting again.

AL.25

Absolute

position erase

Power was switched

on for the first time

in the absolute

position detection

system.

4. Super capacitor of the absolute

position encoder is not charged

After leaving the alarm occurring for a few

minutes, switch power off, then on again.

Always make home position setting again.

1. Wrong setting of parameter No. 0

Set correctly.

2. Built-in regenerative brake resistor

or regenerative brake option is not

connected.

Connect correctly

3. High-duty operation or continuous

regenerative operation caused the

permissible regenerative power of

the regenerative brake option to be

exceeded.

Checking method

Call the status display and check
the regenerative load ratio.

1. Reduce the frequency of positioning.

2. Use the regenerative brake option of

larger capacity.

3. Reduce the load.

4. Power supply voltage is abnormal.

MR-J2S- CL:260VAC or more

MR-J2S- CL1:135VAC or more

Review power supply

Permissible

regenerative power

of the built-in

regenerative brake

resistor or

regenerative brake

option is exceeded.

5. Built-in regenerative brake resistor

or regenerative brake option

faulty.

Change servo amplifier or regenerative

brake option.

AL.30

Regenerative

alarm

Regenerative

transistor fault

6. Regenerative transistor faulty.

Checking method

1) The regenerative brake option
has overheated abnormally.
2) The alarm occurs even after
removal of the built-in
regenerative brake resistor or
regenerative brake option.

Change the servo amplifier.