5 replacing a fan module, Replacing a fan module – Sun Microsystems Sun Fire X4100 User Manual

Page 155

Advertising
background image

Chapter 4

Maintaining the Sun Fire X4200 Server

4-25

4.4.5

Replacing a Fan Module

Follow these steps to remove and replace an individual fan module.

Note –

This component is a hot-swappable CRU and can be replaced by anyone.

TABLE 4-5

lists the qualified part numbers for this component. These part numbers

are subject to change over time. For the most up-to-date list of replaceable
components, product updates, and downloads, see the following URL:

http://www.sun.com/servers/entry/x4100/downloads.jsp

Caution –

The fans are hot-swappable and can be removed and replaced while the

system is running. Do not hold the fan bay door open for more than 60 seconds at a
time to avoid overheating the server. Remove and replace only one fan at a time.

The internal system software designation of the fan connector boards, or fan trays
(FT), and fan modules (FM) is shown in

FIGURE 4-20

(viewed from the front of the

server).

FIGURE 4-20

System Designation of Fan Connector Boards and Fan Modules

1. If the server is in a rack, slide it far enough from the rack so that you can open the

fan bay door. If you cannot safely view and access the component, remove the
server from the rack.

TABLE 4-5

Sun Fire X4200 Supported Fan Module Part Numbers

Component

Part Number

Fan tray assembly (Sun Fire X4200 fan module)

541-0269

Front of server

FT1
FM0

FT1
FM1

FT1
FM2

FT0
FM0

FT0
FM1

FT0
FM2

Advertising