4 ups – Accusys ExaRAID GUI User Manual

Page 110

Advertising
background image

Using the RAID GUI

2-70

Click Close to close the window.

Record Event Log

Click Configure and specify the Lowest severity of events option for the
events you want to record on NVRAM. The events with severity levels
higher than the specified one will be recorded. The default severity level is
info, which means events of all severity levels will be recorded.

Send a Test Mail

Click Configure and specify the Severity of testing event option to send a
test mail. A testing event record will be generated according to the
selected severity level. This helps users to test the event logging and
notifications setup.

2.9.4 UPS

The UPS Control option enables or disables the UPS function when the
controller is started. When this option is set to On, the controller will
automatically detect if the UPS is connected or not.

To configure the UPS settings, do the following:

1. Select Event management > UPS from the main menu, you can view

the UPS information, status, and battery status here.

2. Click Configure and specify the following options.

Note

The event log file stores details of controller activity. In the case of
malfunction, this data can be analysed by the user to determine the
cause(s).

Note

Before sending out the test mail, you need to turn on the event
notification and specify the event receivers. (Refer to 2.9.1 Setting
up the SMTP on page 2-65.
)

Change Date
(YYYY/MM/DD)

This option resets the latest battery replacement
date.

Delay
Shutdown
(seconds)

90 / 180 / 270 / 360 / 450 / 540 / 630

When a power failure occurs and the UPS battery
charge is below the normal range, the UPS will
power down after the specified delay time.

Delay Boot
(seconds)

0 / 60 / 120 / 180 / 240 / 300 / 360 / 420

The UPS automatically powers on after the
specified delay time. This avoids branch circuit
overload when AC power returns.