Burkert Type 8056 User Manual

Page 31

Advertising
background image

- 31 -

RS232_485_ETP_MODBUS_BU_REV02.doc

Set command: CKLP0=

n

0:OK if parameters accepted

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

or sets the value for the six

coefficients for the linearization of
the positive flow rate range.
NOTE: the examples refer to the

command CKLP0, but the others
are the same

Help command: CKLP0=?

min <> max

if accepted

5:ACCESS ERR if insufficient access

level

Read command: CKLN0?

Value of the coefficient if accepted
5:ACCESS ERR if insufficient access

level

Set command: CKLN0=

n

0:OK if parameters accepted
2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

CKLN0, CKLN1, CKLN2, CKLN3,
CKLN4, CKLN5
(Coefficient KL

Negative 0, 1, 2, 3, 4 an 5) Reads
or sets the value for the six
coefficients for the linearization of

the negative flow rate range.
NOTE: the examples refer to the

command CKLN0, but the others
are the same

Help command: CKLN0=?

min <> max

if accepted

5:ACCESS ERR if insufficient access
level

SFREQ (Sampling FREQuency)

Reads or sets the measure sampling
frequency of the instrument.

Read command: SFREQ?

Value of the measure sampling

frequency
5:ACCESS ERR if insufficient access

level

Read command: CRVRF?

Value of the coil regulator voltage
reference

5:ACCESS ERR if insufficient access
level

CRVRF (Coil Regulator Voltage
ReFerence) Reads or sets the value

of the reference for the coil current
regulator.

Help command: CRVRF=?

min <> max

if accepted

5:ACCESS ERR if insufficient access
level

Read command: CRRMA?

Value of the coil regulator margin
5:ACCESS ERR if insufficient access

level

CRRMA (Coil Regulator Regulation
MArgin) Reads or sets the value of

the regulation margin for the coil
current regulator.

Help command: CRRMA=?

min <> max

if accepted

5:ACCESS ERR if insufficient access

level

Read command: EPDEN?

State of the pipe detection circuit

5:ACCESS ERR if insufficient access
level

Set command: EPDEN=

n

0:OK if parameters accepted

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

EPDEN (Empty Pipe Detection

ENable) Enables or disables the
empty pipe detection circuit.

Help command: EPDEN=?

0:OFF,1:ON if accepted
5:ACCESS ERR if insufficient access

level

Read command: EPDGV?

Value of the empty pipe detection gain
5:ACCESS ERR if insufficient access

level

EPDGV (Empty Pipe Detection
Gain Value) Reads or sets the value

of the gain for the empty pipe
detection circuit.

Help command: EPDGV=?

min <> max

if accepted

5:ACCESS ERR if insufficient access

level

Advertising