Burkert Type 8056 User Manual

Page 74

Advertising
background image

- 74 -

RS232_485_ETP_MODBUS_BU_REV02.doc

Bit 3 = min alarm delta T

Bit 4 = max alarm temp. T1
Bit 5 = min alarm temp. T1
Bit 6 = max alarm temp. T2

Bit 7 = min alarm temp. T2

(bit 8-15 not used, value = 0)

0025 Flags

ML212:


Bit 0 (LSB) = command error actuator

Bit 1 = deviation error
Bit 2 = Input error AIN1
Bit 3 = Input error AIN2

Bit 4 = manual regulation active
Bit 5 = safety mode active


(bit 6-15 not used, value = 0)




Data Logger values

Addresses(Hex format)

Description

0064-0077

Data block record n.1 of the Data logger

0078-008B

Data block record n.2 of the Data logger

… …
… …
… …
02D0-02E3

Data block record n.32 of the Data logger


In the following table there is the description of the structure of data of the first generation of the

Data Logger, the following records are the same but in different addresses respect the new
version.


Addresses(Hex format)

Description

0064-0065

Date and time of the record in second (long)

0066-0067

Totalizer value positive (long)

0068-0069

Totalizer value negative (long)

006A-006B

Flow rate in technical unit (float)

006C-006D

Energy value pos. (ML211) (long) / Input AIN1 (float)

006E-006F

Energy value neg. (ML211) (long) / Input AIN2 (float)

0070-0071

Thermal power in technical unit (ML211) (float)

0072-0073

Delta T value in technical unit (ML211) (float)

0074-0075

Temperature value T1 in technical unit (ML211)
(float)