Burkert Type 8056 User Manual

Page 39

Advertising
background image

- 39 -

RS232_485_ETP_MODBUS_BU_REV02.doc

Read command: EPDAT?

Value of empty pipe threshold if

accepted
5:ACCESS ERR if insufficient access
level

Set command: EPDAT=

n

0:OK if parameters accepted
2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

EPDAT (Empty Pipe Detection

Alarm Threshold) Reads or sets the
value of the alarm threshold for the
empty pipe detection system.

Help command: EPDAT=?

min <> max (units)

if accepted

5:ACCESS ERR if insufficient access
level

Read command: OCACV?

Value of alarm current output if

accepted
1:CMD ERR if current output not

enabled
5:ACCESS ERR if insufficient access
level

Set command: OCACV=

n

0:OK if parameters accepted
1:CMD ERR if current output not
enabled

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

OCACV (Output Current Alarm

Condition Value) Reads or sets the
value of the alarm value at which

the current output will be set in
case of error conditions. Valid only if
the current output is installed and

enabled.

Help command: OCACV=?

min <> max (units)

if accepted

1:CMD ERR if current output not

enabled .
5:ACCESS ERR
if insufficient access

level

COMMANDS AND FUNCTIONS EQUIVALENT TO THE “5-INPUTS” MENU

Name and description

Modes

Returned values or codes

Read command: VTTPE?

Status of reset consent if accepted
1:CMD ERR if digital input not
enabled

5:ACCESS ERR if insufficient access
level

Set command: VTTPE=

n

0:OK if parameters accepted
1:CMD ERR if digital input not
enabled

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

VTTPE (Volume Totalizer Total
Positive reset Enable) Enables or
disables the consent for resetting

the total positive volume totalizer
when receiving an external signal

on the digital input. Valid only if
the digital input is installed and

enabled.

Help command: VTTPE=?

List of

num:description

if accepted

1:CMD ERR if digital input not

enabled
5:ACCESS ERR if insufficient access

level

VTPPE (Volume Totalizer Partial
Positive reset Enable) Enables or

disables the consent for resetting
the partial positive volume totalizer
when receiving an external signal

Read command: VTPPE?

Status of reset consent if accepted
1:CMD ERR if digital input not

enabled
5:ACCESS ERR if insufficient access
level

Advertising