Burkert Type 8056 User Manual

Page 75

Advertising
background image

- 75 -

RS232_485_ETP_MODBUS_BU_REV02.doc

0076-0077

Temperature value T2 in technical unit (ML211)

(float)

The returned values are at FFFFFFFF (hex) when the request data is not valid in the

data logger (data not still collected).

Data Logger events

Addresses(Hex format)

Description

03E8-03EB

Data block record n.1 of the Event logger

03EC-03EF

Data block record n.2 of the Event logger

… …
… …
… …
04E4-04E7

Data block record n.64 of the Event logger



In the following table there is the description of the data structure of the first generation of the
event logger, the following records are the same but in different addresses respect the new

version.

Addresses(Hex format)

Description

03E8-03E9

Date/Time of the record in seconds (long)

03EA-03EB Events

(long):


Bit 0 = err. Temp. probe (ML211) / Batch Alarm

Bit 1 = max alarm flow rate
Bit 2 = min alarm flow rate
Bit 3 = scale range value overflow

Bit 4 = output saturated impulses
Bit 5 = input error measurement

Bit 6 = measuring tube empty
Bit 7 = coils excitation interrupted

Bit 8 = max alarm thermal power (ML211)
Bit 9 = min alarm thermal power (ML211)
Bit10 = max alarm delta T (ML211)

Bit11 = min alarm delta T (ML211)
Bit12 = max alarm temp. T1 (ML211)

Bit13 = min alarm temp. T1 (ML211)
Bit14 = max alarm temp. T2 (ML211)
Bit15 = min alarm temp. T2 (ML211)

Bit16 = current loop 4-20 mA interrupted
Bit17 = power supply error

Bit18-23 = not used, value = 0
Bit24 = command error actuator (ML212)

Bit25 = deviation error (ML212)
Bit26 = input error AIN1 (ML212 / ML210 opz.)
Bit27 = input error AIN2 (ML212 / ML210 opz.)

Bit28 = manual setting (ML212)
Bit29 = safety output regulator (ML212)

Bit30-31 = not used, value = 0