Burkert Type 8056 User Manual

Page 73

Advertising
background image

- 73 -

RS232_485_ETP_MODBUS_BU_REV02.doc

Addresses(Hex format)

Description

0000-0001

Flow rate in % (float)

0002-0003

Flow rate in technical unit (float)

0004-0005

Totalizer for total volume positive T+ (V+ for ML211)
(long)

0006-0007

Totalizer for partial volume positive P+ (V- for ML211)
(long)

0008-0009

Totalizer for total volume negative T- (E+ for ML211)

(long)

000A-000B

Totalizer for partial volume negative P- (E- for ML211)
(long)

000C-000D

Clock value in seconds (long)

000E-000F

Input value AIN1 in technical unit (opt.) (float)

0010-0011

Input value AIN2 in technical unit (opt.) (float)

0012-0013

Thermal power value in % (ML211) (float)

0014-0015

Thermal power value in technical unit (ML211) (float)

0016-0017

Delta T value in technical unit (ML211) (float)

0018-0019

Temperature value T1 in technical unit (ML211) (float)

001A-001B

Temperature T2 value in technical unit (ML211) (float)

001C-001D

Set-point value in % (ML212) (float)

001E-001F

Output value in % (ML212) (float)

0020-0021

Deviation value in % (ML212) (float)

0022

Process flags:

Bit 0 (LSB) = excitation is too fast for the sensor
connected / temperature error ML211
Bit 1 = max alarm is active

Bit 2 = min alarm is active
Bit 3 = flow rate exceeds the scale range, overflow

Bit 4 = too many impulse to emit
Bit 5 = measurement signal is disturbed or sensor
disconnect

Bit 6 = empty tube
Bit 7 = coils not working or sensor disconnect

Bit 8 = second measurement scale is active
Bit 9 = flow rate is lower than the cut-off threshold

Bit10 = flow rate negative
Bit11 = new measurement value is available for the
display

Bit12 = counter block signal is active
Bit13 = batch in progress

Bit14 = calibration cicle in progress
Bit15 (MSB) = flow rate simulation in progress

0023

Input Flags AIN1/2:


Bit 2 = input error AIN1

Bit 3 = input error AIN2
(bit 0-1 e 4-15 not used, value = 0)

0024

Flags ML211:

Bit 0 (LSB) = max alarm thermal power

Bit 1 = min alarm thermal power
Bit 2 = max alarm delta T