RS232_485_ETP_MODBUS_BU_REV02.doc

0x34 ‘4’
0x20 ‘

0x32 ‘2’
0x30 ‘0’
0x30 ‘0’
0x38 ‘8’
0x0D Carriage

return

0x0A Line

feed

0x73 Modbus

checksum

0xFE Modbus

checksum


The model and the software version of the converter returned is: “ML 110 VER.3.60 Apr 14 2008”


--------------------------------------------------------------------------------------------------------------------------------------


Example of the sequence of bytes for set the Nominal Diameter of the converter with the function
110 and the ETP command: PDIMV.

In this example the address of the converter is 0x01.

The MODBUS master send this sequence of bytes to the converter for setting the nominal diameter
to the value 10 mm :

01 6E 50 44 49 4D 56 3D 31 30 0D 0D A0 61


Byte (hex format)

Description

01

Address of the converter

6E

Function 110(dec) = 0x6E(hex)

50

‘P’

44

‘D’

49

‘I’

4D

‘M’

56

‘V’

3D

‘=’

31

‘1’

30

‘0’

0D

Character 13

A0

Modbus checksum

61

Modbus checksum

Example of the returned string form the converter:

01 6E 30 3A 4F 4B 0D 0A 31 A1

Byte (hex format)

Description

01

Address of the converter

6E

Function 110(dec) = 0x6E(hex)

30 ‘0’
3A ‘:’
4F ‘O’
4B ‘K’
0D

Carriage return

0A

Line feed

31

Modbus checksum

A1

Modbus checksum