Burkert Type 8056 User Manual

Page 55

Advertising
background image

- 55 -

RS232_485_ETP_MODBUS_BU_REV02.doc

Set command: MSIEN=

n

0:OK if parameters accepted

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

Help command: MSIEN=?

List of

num:description

if accepted

5:ACCESS ERR if insufficient access

level

Read command: STBYC =?

List of

num:description

if accepted

5:ACCESS ERR if insufficient access

level

STBYC (STandBY Command) set
converter in stand-by mode

Once this command is issued ,
the only way to wakeup the
converter is by the keyboard

Set command: STBYC =

n

0:OK if parameters accepted
2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

COMMANDS AND FUNCTIONS EQUIVALENT TO THE “11-INTERNAL DATA” MENU

Name and description

Modes

Returned values or codes

Read command: L2ACD?

Programmed code if accepted

5:ACCESS ERR if insufficient access
level

Set command: L2ACD=

n

0:OK if parameters accepted

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

L2ACD (Level 2 Access CoDe)

Reads or sets the level 2
programmable access code. It can
be set to zero to disable all L2

access requests. WARNING: do
not forget the code entered!

Help command: L2ACD=?

min <> max

if accepted

5:ACCESS ERR if insufficient access

level

Read command: NOT
SUPPORTED

1:CMD ERR if command is issued

Set command: LFDIC=1

0:OK if parameters accepted
2:PARAM ERR if

n

not equal to 1

3:EXEC ERR if default data corrupted

5:ACCESS ERR if insufficient access
level

LFDIC (Load Factory Defaults
Immediate Command) Loads the

factory default parameters.
WARNING: all the current

working parameters eventually
modified by the user will be
lost!

Help command: LFDIC=?

1:EXECUTE

if accepted

5:ACCESS ERR if insufficient access
level

Read command: NOT
SUPPORTED

1:CMD ERR if command is issued

Set command: LUDIC=1

0:OK if parameters accepted
2:PARAM ERR if

n

not equal to 1

3:EXEC ERR if user data corrupted

5:ACCESS ERR if insufficient access
level

LUDIC

(Load

User

Data

Immediate Command) Loads the
user preset parameters.

WARNING: all the current
working parameters eventually

modified by the user will be
lost!

Help command: LUDIC=?

1:EXECUTE

if accepted

5:ACCESS ERR if insufficient access
level

Read command: NOT
SUPPORTED

1:CMD ERR if command is issued

SUDIC

(Save

User

Data

Immediate Command) Saves the
current working parameters as user

preset data.

Set command: SUDIC=1

0:OK if parameters accepted

2:PARAM ERR if

n

not equal to 1

3:EXEC ERR if memory failure
5:ACCESS ERR if insufficient access

level

Advertising
This manual is related to the following products: