- 78 -

RS232_485_ETP_MODBUS_BU_REV02.doc


Example of the sequence of bytes for return the model and the software version of the converter
with the function 110 and the ETP command: MODSV.

In this example the address of the converter is 0x01.
ETP command is not case sensitive, “MODSV?” = “modsv?”

The MODBUS master send this sequence of bytes to the converter for reading the model and the

software version: 01 6E 6D 6F 64 73 76 3F 0D 6F FE

Byte (hex format)

Description

0x01

Address of the converter

0x6E

Function 110(dec) = 0x6E(hex)

0x6D ‘m’
0x6F ‘o’
0x64 ‘d’
0x73 ‘s’
0x76 ‘v’
0x3F ‘?’
0x0D Character

13

0x6F Modbus

checksum

0xFE Modbus

checksum





Example of the returned string form the converter:

Byte (hex format)

Description

0x01

Address of the converter

0x6E

Function 110(dec) = 0x6E(hex)

0x4D ‘M’
0x4C ‘L’
0x20 ‘

0x31 ‘1’
0x31 ‘1’
0x30 ‘0’
0x20 ‘

0x56 ‘V’
0x45 ‘E’
0x52 ‘R’
0x2E ‘.’
0x33 ‘3’
0x2E ‘.’
0x36 ‘6’
0x30 ‘0’
0x20 ‘

0x41 ‘A’
0x70 ‘p’
0x72 ‘r’
0x20 ‘

0x31 ‘1’