Edwards Signaling FSC Series User Manual

Page 100

Advertising
background image

Appendix B: Programming templates

92

FSC Series Technical Reference Manual

IDC 7 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000007

1A EA

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000007

2A EA

Trouble

None 

1

2

1 & 2

(1/3)37300007

7A FA

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000007

3A EA

Monitor zone active

None 

1

2

1 & 2

(1/3)40000007

5A EA

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.

IDC 8 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000008

18 E8

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000008

28 E8

Trouble

None 

1

2

1 & 2

(1/3)37300008

78 F8

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000008

38 E8

Monitor zone active

None 

1

2

1 & 2

(1/3)40000008

58 E8

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.