Chapter 3: Panel programming

FSC Series Technical Reference Manual

33

RRM Multi Mode:

Determines how relays on an FSRRM24 configured for

programmable operation (jumper installed on JP2) are programmed. The values
that you can select are:

Common Alarm:

Relays are automatically programmed to energize on any

alarm event.

Matrix:

You must program an initiating device circuit to activate the relays.

Table 11: Panel program options

Step Option

Values

LCD first line

ALARM

TROUBLE

SUP

POWER

DISABLE

LCD second line

WATERFLO

W

ANN TROUBL

E

BATT TROUBLE

GND FAULT

SERVICE DETECTOR

1

Load Defaults

    No

(default)

   

Yes

   

2

Edit Passcode [3]

   

1111 (default) to FFFF

   

3

Enable Passcode [2]

    No

(default)

   

Yes

   

4

Panel Op Mode [2]

    FACP

(default)

   

FACOM

   

Sprinkler

Supv

  

5

Rst/Sil Inhibit

    None

(default)

   

1

minute

   

6

AC Fail Delay

    0

hours

   

1

hour

   

2

hours

   

3

hours

(default)

  

4

hours

   

5

hours

   

6

hours

   

7

hours

  

8

hours

   

9

hours

   