UL 864 programming requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, certain programming features or options must be limited to specific values or not used at all
as indicated below.

Programmable
feature or option

Permitted in
UL 864? (Y/N)

Possible
settings

Settings permitted
in UL 864

AC fail delay

Y

0 to 15 hours

1, 2, or 3 hours

Electronic waterflow
retard

Y

0 to 150 seconds

0 to 90 seconds

Nonlatching alarm
circuits

Y No

Yes

No
Yes [1]

NAC wiring class

Y

A
B
Parallel

Yes
Yes
No

Telephone line
supervision duration

Y

0 to 200 seconds

1 to 200 seconds

Telephone line ground
fault supervision

Y No

Yes

Yes

Test signal frequency

Y

0 to 45 days

1 (daily)

Dialer mode

Y

Dual line
Single line
Modem/LCD
LCD only

Dual line
Single line [2]
Modem/LCD [3]
LCD only [3]

Send event restore
codes

Y Send

Restores

No Restores

Send Restores

[1] Allowed only when the IDC is connected to a latching alarm device

[2] Allowed only when the supervising station supervises the telephone line and annunciates fault
conditions within 200 seconds

[3] Prohibited when the control panel is connected to a supervising station