Edwards Signaling FSC Series User Manual

Page 98

Advertising
background image

Appendix B: Programming templates

90

FSC Series Technical Reference Manual

IDC 3 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000003

13 E3

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000003

23 E3

Trouble

None 

1

2

1 & 2

(1/3)37300003

73 F3

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000003

33 E3

Monitor zone active

None 

1

2

1 & 2

(1/3)40000003

53 E3

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.

IDC 4 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000004

14 E4

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000004

24 E4

Trouble

None 

1

2

1 & 2

(1/3)37300004

74 F4

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000004

34 E4

Monitor zone active

None 

1

2

1 & 2

(1/3)40000004

54 E4

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.