Chapter 3: Panel programming

30

FSC Series Technical Reference Manual

To change the passcode:

1. Select the Edit Passcode option.

2. Enter the new passcode.

A passcode consists of four characters. Valid characters are the numbers 0 to
9 and the letters A to F.

Detecting remote modules

Use the Find Peripherals option to detect which remote modules are connected
to the control panel when you first configure the control panel and anytime you
add or remove remote modules from the system.

Note:

Do not remove the jumper on J3 (PRG) until the control panel has

completed the detection process. If you do, you must remove all power from the
panel before you can enter local programming mode again.

To detect remote modules:

1. Select the Find Peripherals option.

2. Enter Yes.

The bottom status LEDs will flash until the control panel has completed the
detection process. This may take up to 40 seconds. When finished, the
control panel displays how many remote modules were detected, as shown in
Table 10.

Table 10: Find Peripherals results

Step Option

Values

LCD first line

ALARM

TROUBLE

SUP

POWER

DISABLE

LCD second line

WATERFLO

W

ANN TROUBL

E

BATT TROUBLE

GND FAULT

SERVICE DETECTOR

9

Find Peripherals

   

was XX now 00

   

was XX now 01

   

was XX now 02

   

was XX now 03

  

was XX now 04

   