Setting nac 4/2 event activation code options – Edwards Signaling FSC Series User Manual

Page 66

Advertising
background image

Chapter 4: Dialer programming

58

FSC Series Technical Reference Manual

Table 22: IDC 4/2 event activation code options

Option Description

Values

IDC Alm CDE

Determines the 4/2 code that the dialer
transmits when the IDC is activated and
the IDC is an alarm-verified or alarm-
unverified zone type

0 to 9, and A to F

Default: 1<n> where n is the 1
to 9 (IDC 1 to 9), and A (IDC
10)

IDC WF CDE

Determines the 4/2 code that the dialer
transmits when the IDC is activated by a
waterflow switch and the IDC is a
waterflow, waterflow-retard, waterflow/
supervisory, or waterflow-
retard/supervisory zone type

0 to 9, and A to F

Default: 2<n> where n is the 1
to 9 (IDC 1 to 9), and A (IDC
10)

IDC Trb CDE

Determines the 4/2 code that the dialer
transmits when the IDC wiring is open

0 to 9, and A to F

Default: 7<n> where n is the 1
to 9 (IDC 1 to 9), and A (IDC
10)

IDC Sup CDE

Determines the 4/2 code that the dialer
transmits when the IDC is activated by a
supervisory device and the IDC is a
supervisory, waterflow/ supervisory, or
waterflow-retard/supervisory zone type

0 to 9, and A to F

Default: 3<n> where n is the 1
to 9 (IDC 1 to 9), and A (IDC
10)

IDC Mon CDE

Determines the 4/2 code that the dialer
transmits when the IDC is activated and
the IDC is monitor zone type

0 to 9, and A to F

Default: 3<n> where n is the 1
to 9 (IDC 1 to 9), and A (IDC
10)

Setting NAC 4/2 event activation code

options

Table 23 lists the set of NAC 4/2 event activation code options and their default
values.

Review Table 23 and make changes as required.

Table 23: NAC 4/2 event activation codes

Option Description

Values

NAC Trb CDE

Determines the 4/2 code that the dialer
transmits when the NAC wiring is open or
shorted

0 to 9, and A to F

Default: 6<n> where n is the 1
to 4 (NAC 1 to 4)