Performing lamp tests, Trouble messages, Panel lamp test – Edwards Signaling FSC Series User Manual

Page 73: Fsrsi, fsrzi-a, and fsrzi-sa lamp test

Advertising
background image

Chapter 5: Maintenance

FSC Series Technical Reference Manual

65

Performing lamp tests

Panel lamp test

A panel lamp test turns on all the LEDs on the panel and on FSRSI, FSRZI-A,
and FSRZI-SA modules so you can verify their proper operation.

To test panel LEDs:

1. Press and hold the Remote Disconnect and Walk Test buttons

simultaneously.

2. Verify that all LEDs on the panel turn on.

If a dialer is installed, the LCD displays:
DB# xx P:x.yy.zz
D:x.yy.zz

Where:

DB# is the database revision number

P:x.yy.zz is the main panel version

D:x.yy.zz is the F-DACT(F) version

FSRSI, FSRZI-A, and FSRZI-SA lamp test

FSRSI, FSRZI-A, and FSRZI-SA modules can be installed individually or in
groups to create a complete remote annunciator. You can perform a local lamp
test on the FSRSI, FSRZI-A, and FSRZI-SA. An FSRSI is required to initiate this
function.

To test FSRSI and FSRZI-A LEDs:

1. Press and hold the FSRSI Silence button for five seconds.

2. Verify that all LEDs on the FSRSI and FSRZI-A modules turn on.

Trouble messages

Table 24: Possible causes of trouble messages

Message Possible

cause

Peripheral trouble

The panel lost communications with the peripherals.