Chapter 2: Installation

20

FSC Series Technical Reference Manual

Installing remote modules

Figure 6 shows the maximum number of devices that you can install on the
remote module communication bus. Refer to the installation sheet provided with
the remote module for mounting and wiring instructions. Wiring diagrams are also
provided in Appendix C.

Figure 6: Remote module bus block diagram

Important points

• You can only install one FSRRM24 configured for common relay operation

(jumper installed on JP5) per peripheral group.

• You can only install zone indicator modules for zones 6 to 10 on ten-zone

control panels.

• For ten-zone control panels, you can install an F-series remote annunciator in

place of the FSRSI and the two zone indicator modules (FSRZI-A or
FSRZI-SA).

• If the remote modules require more power than the control panel can provide,

use a power-limited and regulated 24 VDC auxiliary/booster power supply
that is UL/ULC Listed for fire protective signaling systems to power all or
some of the remote modules.

Power

Data

FSRSI

FSRZI-A

or

FSZRI-SA

FSRRM24

FSRRM24

FSRRM24

FSRRM24

FACP

Peripheral group 1

Zones

1 to 5

FSRZI-A

or

FSZRI-SA

Zones

6 to 10

Common

relay

Zones

1 to 5

Zones

6 to 10

Matrix

FSRSI

or

FSUIM

FSRZI-A

or

FSZRI-SA

FSRRM24

FSRRM24

FSRRM24

FSRRM24

Peripheral group 2

Zones

1 to 5

FSRZI-A

or

FSZRI-SA

Zones

6 to 10

Common

relay

Zones

1 to 5

Zones

6 to 10

Matrix