Edwards Signaling FSC Series User Manual

Page 45

Advertising
background image

Chapter 3: Panel programming

FSC Series Technical Reference Manual

37

events when a supervisory device is activated. Select this zone type when the
IDC is connected to waterflow switches and supervisory devices.

Supervisory:

Activates supervisory events. Select this zone type when the

IDC is connected to supervisory devices.

Monitor:

Activates monitor events. Select this zone type when the IDC is

connected to dry contact devices that monitor the operation of ancillary
system functions.

Note:

The monitor zone type is not approved for use in Canada under ULC 527.

Remote SigSil/Drill:

Activates the Signal Silence or Drill command. Select

this zone type when the IDC is connected to momentary switches that are
used to silence or activate notification appliances from a remote location.

Remote AC Fail:

Activates trouble events when the trouble relay on an

auxiliary/booster power supply remains closed for as long as the panel’s AC
fail delay setting. Select this zone type when the IDC is connected to
auxiliary/booster power supply trouble relays that only close when AC power
fails.

Cross Zoned:

Activates alarm events only when two zones are activated.

Select this zone type when the IDC is connected to two-wire smoke detectors,
dry contact devices, or both and multiple detector operation is required. For
more information, see Figure 30 on page 113.

IDC Class:

Determines if the IDC is wired Class A or Class B.

IDC Non-Latching:

Determines if alarm, waterflow, or supervisory zone types

are latching or nonlatching circuits. Monitor and other zone types are always
nonlatching.

Note:

To meet UL 864 9th edition requirements, nonlatching alarm circuits are

only allowed when connected to a latching alarm device.

IDC Service Chk:

Determines if the panel indicates when an ESL model detector

needs servicing.

IDC RRM Relay:

Determines which relays on a remote relay module the IDC

turns on. Available only when the panel’s RRM multi mode option is set to Matrix.

IDC Code Digit 1:

Determines the first set of pulses in a coded alarm signal. The

IDC Code Digit options are only available when a notification appliance circuit’s
NAC type option is set for Coder.

IDC Code Digit 2:

Determines the second set of pulses in a coded alarm signal.

IDC Code Digit 3:

Determines the third set of pulses in a coded alarm signal.

IDC Code Digit 4:

Determines the fourth set of pulses in a coded alarm signal.

Advertising