Chapter 1: System overview and operation

FSC Series Technical Reference Manual

15

After enabling an IDC, alarms from that IDC are inhibited for 30 seconds. During
this time, the IDC can be disabled to avoid an unwanted alarm.

To enable a disabled IDC or NAC:

1. Press the Disable button for the IDC or NAC you want to enable.

Using the drill command

You can use the drill command to activate all of the notification appliance circuits.
Pressing Drill activates all audibles and visibles according to the panel
programming, but does not activate the panel’s common alarm relay. The F-
DACT(F) can be programmed to transmit a drill condition, but it will never report
the drill as an alarm. Drill will not operate with an active alarm or supervisory
event at the panel.

To perform a fire drill:

1. Press and hold the Signal Silence & Drill button for one second.

2. To stop the drill, press and hold the Signal Silence & Drill button for one

second.