Appendix A: System calculations
72
FSC Series Technical Reference Manual
Form A
Module
Quantity
Standby
current (mA)
Qty X Standby
current (mA)
Alarm
current (mA)
Qty X Alarm
current (mA)
FSRSI
17
56
FSRZI-A or FSRZI-
SA
8
76
FSRRM24
(common)
26
70
FSRRM24
(zone)
10
70
FSUIM
53
114
FSRA10(F)/
FSRA10C(F)
17
98
Other
AUX
Total AUX [2]
1. The maximum number of remote modules that you can install varies with the control panel model.
[2] If Total AUX exceeds 500 mA, use an auxiliary/booster supply to share some of the load. See
“Connecting an auxiliary/booster power supply“ on page 22.