Appendix A: System calculations

72

FSC Series Technical Reference Manual

Form A


Module

Quantity

Standby

current (mA)

Qty X Standby

current (mA)

Alarm

current (mA)

Qty X Alarm

current (mA)

FSRSI

17

56

FSRZI-A or FSRZI-
SA

8

76

FSRRM24

(common)

26

70

FSRRM24

(zone)

10

70

FSUIM

53

114

FSRA10(F)/
FSRA10C(F)

17

98

Other

AUX

Total AUX [2]

1. The maximum number of remote modules that you can install varies with the control panel model.

[2] If Total AUX exceeds 500 mA, use an auxiliary/booster supply to share some of the load. See
“Connecting an auxiliary/booster power supply“ on page 22.

Form B

IDC

Quantity of

detectors [1]

Detector current

(mA) [2]

Standby current per circuit

(Quantity x Detector current)

IDC 1

IDC 2

IDC 3

IDC 4

IDC 5

IDC 6

IDC 7

IDC 8

IDC 9

IDC 10

Total IDC standby current =

[1] See compatibility list P/N 3101019 for a list of approved detector models and quantities.

[2] Maximum current per IDC may not exceed 3.0 mA.