Edwards Signaling FSC Series User Manual

Page 72

Advertising
background image

Chapter 5: Maintenance

64

FSC Series Technical Reference Manual

• There is no fire protection for the IDC in walk test

If an unselected IDC goes into alarm or trouble, all outputs operate as
programmed.

The IDC you are testing behaves as follows:

• The appropriate panel, FSRSI, and FSRZI-A LEDs and buzzers are turned

on.

• In the audible test mode, the notification appliances sound for a number of

times equal to the zone number.

• After activation, the panel resets the IDC. During the reset period

(approximately eight seconds), the IDC trouble LED flashes rapidly. If the
device being tested is not restored, the IDC does not reset and the LED
continues to flash. If the device is restored (no alarm is present), the panel is
ready to test another device or detector.

• Resettable auxiliary power is deactivated while the zone is reset.

• Input zones programmed as waterflow with retard require 10 to 15 seconds of

activation to initiate the test signals.

• For trouble events, the appropriate LEDs and the buzzers are turned on. In

the audible (NAC) test mode a one-second pulse sounds on the audible
devices. After sounding, the zone resets in preparation for continued testing.

• For ground fault events, the appropriate LEDs and the buzzers are turned on.

In the audible (NAC) test mode a one-second pulse sounds on the audible
devices. After sounding, the zone resets in preparation for continued testing.

To perform a walk test:

1. Press the Walk Test button once to perform an audible walk test.

— or —

Press the Walk Test button twice to perform a silent walk test.

2. Press the Disable button for the IDC you want to test.

3. Conduct your walk test for the IDC.

4. When you are finished testing an IDC, press the Disable button to turn off the

walk test for that IDC.

5. Select another IDC to walk test (steps 2 through 4) or exit from the walk test

by pressing the Walk Test button.

Advertising