Battery calculation worksheet – Edwards Signaling FSC Series User Manual

Page 78

Advertising
background image

Appendix A: System calculations

70

FSC Series Technical Reference Manual

Battery calculation worksheet

Use this worksheet to determine the minimum size required for the panel’s
standby batteries. Obtain operating current requirements for initiating devices
and notification appliances from their respective installation sheets.

Battery calculation worksheet

Standby

Current (mA)

Alarm

Current (mA)

Base panel [1]

F-DACT(F) (optional)

(65 mA)

(107 mA)

AUX current (see Form A)

IDC detector current [3]

NAC 1 load

0

NAC 2 load

0

NAC 3 load

0

NAC 4 load

0

Total current [6]

Required standby and
alarm time (in hours)

Standby
time [4]

Alarm time [5]

mAh

+

mAh

=

mAh

 1000

Battery amp hour total =

Ah

 1.2

Minimum

battery size [2]

Ah

Advertising