Chapter 2: Installation

22

FSC Series Technical Reference Manual

Receiver compatibility

The F-DACT(F) is listed for use with the receivers shown below.

Table 9: Receiver models and formats

Manufacturer Model

Format

Ademco

685

EST 4/2, Contact ID

FBII

CP220

EST 4/2, Contact ID

Osborne-Hoffman

OH 2000

EST 4/2, Contact ID

Radionics D6500

D6600

EST 4/2
EST 4/2. Contact ID

Silent Knight

9000

EST 4/2

Sur-Gard

MLR1, MLR2, MCDI TLR,
TLR+

EST 4/2, Contact ID

Note:

EST 4/2 is SIA DCS-02 P3 with the ability to transmit hexadecimal event codes.

Connecting an auxiliary/booster power

supply

The control panel can provide up to 0.5 A of AUX power to operate ancillary
equipment. For example, remote modules and graphic annunciator cards. If more
than 0.5 A is required, you must use a power-limited and regulated 24 VDC
auxiliary/booster power supply that is UL/ULC Listed for fire protective signaling
systems to power all or some of the ancillary equipment.

Connect an auxiliary/booster supply to the control panel as shown in Figure 7.