Chapter 3: Panel programming

FSC Series Technical Reference Manual

29

When you finish

After you have finished programming, make sure the panel is not in a trouble
fault state. No trouble LEDs should be turned on. Test all circuits and panel
functions to make sure that the panel is programmed correctly.

Getting started

Restoring panel default settings

Caution:

Restoring panel default settings disables passcode protection. If you

want passcode protection you must enable it again.

Note:

Restoring panel default settings doesn’t change the passcode and doesn’t

restore dialer default settings.

Control panels are shipped from the factory with default settings for a typical
system. Use the Load Defaults option to restore the panel default settings.

To restore panel default settings:

1. Select the Load Defaults option.

2. Enter Yes.

Enabling passcode protection

Passcode protection prevents unauthorized access to the panel’s programming.
The default passcode is 1111.

This option is only available when a dialer is installed.

To enable passcode protection:

1. Select the Enable Passcode option.

2. Enter Yes.

Changing the passcode

After enabling the passcode, you should change it at your earliest convenience.
Write down the new passcode and store it in a safe place.

This option is only available when a dialer is installed and the passcode is
enabled.